On the input side (see also Inverter Operating Limits):
-The inverter should search for the Maximum Power Point of the array (MPP tracking), i.e. permanently adjust the
operating Voltage in order to draw the higher possible power from
the array.
This MPP tracking can be performed in a voltage window defined by
the VmppMin and VmppMax parameters.
-When the true
MPP voltage of the array is outside of these
limits:
in "Limitation"
mode, the voltage will be clipped to the VmppMin or VmppMax value
(most of the modern inverters). The IL_Vmin and IL_Vmax losses
will be the difference between the true MPP of the array and this
clipped operating point power.
in "Cut" mode, the
inverter will simply stop working. The full MPP array power is
lost.
-The production begins as soon
as the MPP power is over the power threshold Pthresh of the
inverter. The MPP power below this threshold is accounted as
IL_Pmin loss. It is usually less that 0.1% over the
year.
PVsyst doesn't manage a Voltage
threshold, as the Array voltage is not very dependent on the
irradiance. Even with a very low irradiance, the array MPP voltage
becomes significant.
The Pthresh power may be understood
as the power required for the Inverter internal circuits
consumption.
Some manufacturers claim for a very
low threshold. We can observe that 0.5% of PNom would correspond to
an irradiance of 5 W/m² (with respect to 1000 W/m²). Please
remember that by very covered weather we have already 30 to 50 W/m²
!
-If the MPP power is
greater than the acceptable input power (PnomDC), the inverter will
clip the operating point to the input power which corresponds to
Pnom(AC).
in "Limitation"
mode, the array voltage will be increased until reaching this
PnomDC. The difference with respect to the MPP virtual power is
accounted as Overload loss
(IL_Pmax).
In "Cut" mode, the
inverter will stop working (very old inverters), so that
the IL_Pmax value is the full MPP power.
As these very old inverters could not
start under full irradiance, the inverter was OFF until the next
day.
In any case this overload operating
mode doesn't mean that the inverter will dissipate the excess
energy: simply this energy is not produced by the array. Therefore
there will be no extra heat, no extra wear of the inverter, it is a
safe behavior.
-The necessary voltage for limiting the power to PNomDC may be over the VmppMax value. In these cases there is no possible operating range, and the inverter has to stop, leading to very high overload loss. Therefore, especially with highly oversized arrays, the normal operating voltage should not be chosen too close to VmppMax.
-When the manufacturer specifies a Minimum voltage for getting the maximum power (VminPnom), this corresponds indeed to an input current limitation, and PVsyst treats this case as such during the simulation. The eventual loss will be accounted as IL_IMax.
-When the manufacturer specifies a Nominal voltage (VmppNom), the sizing will take this condition into account as far as possible, but this is a "weak" condition.
-The Absolute Maximum voltage VAbsMax is the limit voltage acceptable for the input electronics devices: it should never be overcome in any situation.
-Some manufacturers also specify conditions on the PV array: a Maximum value for the ISC (STC) or the Array nominal power. To our mind, these conditions have no real physical meaning since the inverter chooses itself the operating point on the I/V curve. However they may be contractual (affect the warranty), and in these cases they should be satisfied.
On the output side:
-The main basic parameter of the inverter is the Nominal AC power Pnom, that is the maximum power the inverter is able to deliver to the grid in any conditions.
-Some manufacturers specify also a Maximum AC power Pmax, as a power which may be attained in specific conditions. This corresponds to an increase of the authorized nominal power when the ambient temperature is not too high. See the page "Inverter: special output conditions"
-The output (grid) nominal voltage VnomAC is used for the determination of the wiring losses if any (i.e. related to the current). But the specified maximum current value is not used.
-PVsyst doesn't treat the Power transfer to the grid in details. However you can define an external transformer (for MV lines) and its associated losses.
-The real grid voltage is not an accessible input to the simulation, and cannot be modeled of course. Therefore no output voltage limitations can be applied.
-A specified Phase shift may be imposed by the grid operator. This will give rise to the production of Reactive energy. But the output power resulting of the simulation is the active power.
-You can define auxiliary losses (fans, others), active from a specified power threshold, and night consumption. These values will be used as defaults in the Detailed losses.
-Inverters may have a transformer or not. The transformer is a
cumbersome and heavy device. It reduces the efficiency by about 1%
or more.
The transformer allows to reference of the array voltage to the
ground or any given voltage, and makes the array voltage
independent on the Grid voltage.
But inverters with no transformer are not compatible with amorphous
modules (damages the TiO2 layer).